Independently Controlled Domestic Hot Water (DHW) – Packaged Plate Heat Exchanger

SPECIFICATION: Integral Control Panel, Instantaneous Plate Heat Exchanger Pack, Seven Day Timer & Optional Anti-Legionella function.

Primary Side: Three Way Thermostatically Controlled Modulating Valve, Circulation pump, Vent valve, Regulating flow orifice (on the bypass).

Secondary Side: Safety Pressure Relief Valve, Check Valve c/w Thermostatic Sensors

From £1,919.00

To select the Plate heat exchanger most suitable for your system please change the KW output below which will automatically increase or decrease the secondary hot water flow rate.

Clear

Aeltherm DHW - Plate Heat Exchanger

Instantaneous Plate Heat Exchanger c/w Anti-Legionella function, Integrated control panel, 3-way electric power operated modulating valve, Circulation pump, Vent valve, Regulating flow orifice (on the bypass). Secondary DHW Secondary Circuit : Safety Pressure relief valve, Check valve c/w sensors

  • Heat Load 25.2 KW *

    Secondary Flow Rate L/S0.12
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA4
    Primary Heating Flow Rate L/S0.19
    Primary Heating Flow In Temperature oC82
    Primary Flow Out Temperature °C50
    Primary Pressure Drop KPA44 (Covered by the AEL Primary Pump)
    Heat ModelAEL-DHW-020510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers Warranty anteeAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 31.5 KW *

    Secondary DHW Flow Rate L/S0.15
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA6
    Primary Heating Flow Rate L/S0.238
    Primary Heating Temperature In oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA34 (Covered by the AEL Primary Pump)
    Heat ModelAEL-DHW-025510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 44.1 KW *

    Secondary Flow Rate L/S0.21
    Secondary DHW Temperature Flow IN oC 10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA5
    Primary Flow Rate L/S0.33
    Primary Heating Flow In Temperature oC82
    Primary Flow out Temperature °C50
    Primary Pressure Drop KPA36 (Covered by the Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-035510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 56.7 KW *

    Secondary Flow Rate L/S0.27
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA8
    Primary Heating Flow Rate L/S0.43
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA22 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-045510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 69.3 KW *

    Secondary Flow Rate L/S0.33
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA12
    Primary Flow Rate L/S0.53
    Primary Heating Temperature In oC 82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA16 (Covered by the Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-055510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 75.6 KW *

    Secondary DHW Flow Rate L/S0.36
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA8
    Primary Flow Rate L/S0.57
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA21 (Covered by the Pre installed AEL Primary Pump)
    Heat ModelAEL-DHW-060510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 81.9 KW *

    Secondary DHW Flow Rate L/S0.39
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA6
    Primary Heating Flow Rate L/S0.62
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA20 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-065510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 94.5 KW *

    Secondary DHW Flow Rate L/S0.45
    Secondary DHW Flow Temperature In oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA8
    Primary Heating Flow Rate L/S0.716
    Primary Heating Flow In Temperature oC82
    Primary Flow out Temperature °C50
    Primary Pressure Drop KPA20 (Covered By The Pre Installed AEL Primary Pump.
    Heat ModelAEL-DHW-075510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers Warranty AHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 107 KW *

    Secondary DHW Flow Rate L/S0.51
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA7
    Primary Heating Flow Rate L/S0.81
    Primary Heating Flow In Temperature oC82
    Primary Flow out Temperature °C50
    Primary Pressure Drop KPA15 (Covered by the Pre Installed Primary Pump)
    Heat ModelAEL-DHW-085510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1" / G 1"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 123.9 KW *

    Secondary Flow Rate L/S0.59
    Secondary OC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA6
    Primary Flow Rate L/S0.955
    Primary Flow In Temperature oC82
    Primary Flow out Temperature °C50
    Primary Pressure Drop KPA48
    Heat ModelAEL-DHW-100510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1 1/4" / G 1 1/4"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 149.1 KW *

    Secondary DHW Flow Rate L/S0.71
    Secondary DHW Flow In Temperature oC 10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA14
    Primary Heating Flow Rate L/S1.15
    Primary Heating Flow In Temperature oC82
    Primary Flow out Temperature °C50
    Primary Pressure Drop KPA24 (Covered By The AEL Pre Installed Primary Pump)
    Heat ModelAEL-DHW-120510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1 1/4" / G 1 1/4"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 186.9 KW *

    Secondary DHW Flow Rate L/S0.9
    Secondary DHW Flow In Temperature oCOC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA7
    Primary Flow Rate L/S1.43
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA66 ( Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-150510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1 1/4" / G 1 1/4"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 224.7 KW *

    Secondary DHW Flow Rate L/S1.08
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA9
    Primary Heating Flow Rate L/S1.72
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA38 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-180510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1 1/4" / G 1 1/4"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 262.5 KW *

    Secondary DHW Flow Rate L/S1.26
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA19
    Primary Heating Flow Rate L/S2
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA27 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-210510
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1 1/4" / G 1 1/4"
    Secondary Connections In / OutG 1" / G 1"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 300.3 KW *

    Secondary DHW Flow Rate L/S1.45
    Secondary DHW Flow Temperature In oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA21
    Primary Heating Flow Rate L/S2.24
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA27 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-2401410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1 1/2" / G 1 1/4"
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 338.1 KW *

    Secondary DHW Flow Rate L/S1.62
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA17
    Primary Heating Flow Rate L/S2.52
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA19 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-2701410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutG 1 1/2" / G 1 1/4"
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 375.9 KW *

    Secondary DHW Flow Rate L/S1.81
    Secondary DHW Flow In Temperature oC 10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA14
    Primary Heating Flow Rate L/S2.8
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA34 ( Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-3301410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN40 / DN40
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 413.7 KW *

    Secondary DHW Flow Rate L/S1.99
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA17
    Primary Heating Flow Rate L/S3.08
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA18 ( Covered By The AEL Pre Installed Primary Pump)
    Heat ModelAEL-DHW-3301410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN40 / DN40
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 438.9 KW *

    Secondary DHW Flow Rate L/S2.09
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA15
    Primary Heating Flow Rate L/S3.27
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA17 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-3501410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN40 / DN40
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 474.6 KW *

    Secondary DHW Flow Rate L/S2.28
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA17
    Primary Heating Flow Rate L/S3.54
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA34 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-3801410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN40 / DN40
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 512.4 KW *

    Secondary DHW Flow Rate L/S2.47
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA15
    Primary Heating Flow Rate L/S3.82
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA31 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-4101410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN40 / DN40
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 550.2 KW *

    Secondary DHW Flow Rate L/S2.65
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA14
    Primary Heating Flow Rate L/S4.1
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA26 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-4401410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN40 / DN40
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 588 KW *

    Secondary DHW Flow Rate L/S2.83
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA16
    Primary Heating Flow Rate L/S4.39
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow out Temperature °C50
    Primary Pressure Drop KPA23 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-4701410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN40 / DN40
    Secondary Connections In / OutG 1 1/4" / G 1 1/2"
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 625.8 KW *

    Secondary DHW Flow Rate L/S3.01
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA18
    Primary Heating Flow Rate L/S4.67
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA41 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-5001410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN50 / DN50
    Secondary Connections In / OutDN50 / DN50
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 663.6 KW *

    Secondary DHW Flow Rate L/S3.19
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA18
    Primary Heating Flow Rate L/S4.95
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA36 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-5301410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN50 / DN50
    Secondary Connections In / OutDN50 / DN50
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 701.4 KW *

    Secondary DHW Flow Rate L/S3.38
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA19
    Primary Heating Flow Rate L/S5.23
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA29 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-5601410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN50 / DN50
    Secondary Connections In / OutDN50 / DN50
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 751.8 KW *

    Secondary DHW Flow Rate L/S3.62
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow out Temperature °C60
    Secondary Pressure Drop KPA18
    Primary Heating Flow Rate L/S5.61
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA22 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-6001410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN50 / DN50
    Secondary Connections In / OutDN50 / DN50
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 789.6 KW *

    Secondary DHW Flow Rate L/S3.8
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA17
    Primary Heating Flow Rate L/S789.6
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA20 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-6301410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)
    Primary Connections In / OutDN50 / DN50
    Secondary Connections In / OutDN50 / DN50
    Secondary Maximum Working Pressure Bar6
    Manufacturers WarrantyAHRI Units 3 Years, Non AHRI Units 1 Year
  • Heat Load 827.4 KW *

    Secondary DHW Flow Rate L/S3.98
    Secondary DHW Flow In Temperature oC10
    Secondary DHW Flow Out Temperature °C60
    Secondary Pressure Drop KPA14
    Primary Heating Flow Rate L/S6.17
    Primary Heating Flow In Temperature oC82
    Primary Heating Flow Out Temperature °C50
    Primary Pressure Drop KPA18 (Covered By The Pre Installed AEL Primary Pump)
    Heat ModelAEL-DHW-6601410
    Primary Maximum Working Pressure Bar10
    Heat Exchanger MaterialStainless Steel (316)